Maximum tag data link i/o response time – Omron SYSMAC CJ1W-EIP21 User Manual

Page 312

Advertising
background image

286

I/O Response Time in Tag Data Links

Section 10-3

The following table gives the items required to find the I/O response time and
values used in calculations for this system configuration.

Maximum Tag Data Link I/O Response Time

You can find the maximum I/O response time from the total of (1) to (6) in the
following figure.

PLC#1

EtherNet/IP

PLC#2

PLC#3

Node 1

Node 2

Node 3

Input switch (external input device)

Input

W000.01

W000.01

Output

Output relay (external output device)

Tag Data Link Table

PLC#1

PLC#2

PLC#3

Outputs

RPI = 10 ms

RPI = 10 ms

W000

722 words x 16 connections
Total: 11,552 words

W000

Inputs

Inputs

256 words x 16 connections
Total: 4,096 words

RPI = 100 ms

Outputs

Connection 1

Item

Value used in calculation example

PLC#1

PLC#2

External I/O device delay time

Input device delay:
1.5 ms

Output device delay:
2.0 ms

Cable length

50 m

CPU Unit model

CJ2H CPU Unit

CJ2H CPU Unit

RPI

10 msec

---

Number of receive connections

0

32

CPU Unit cycle time

10 msec

15 msec

Total number tag
data link words

Number of send
words

11,552 None

Number of
receive words

None 15,648