281

Adjusting the Communications Load

Section 10-2

Method 3: Changing the Packet Interval (RPI) of Only Specific
Connections

In this example, we want a faster tag data links for just a particular connection
of device 192.168.250.1.

Double-click device 192.168.250.1 in the Network Configuration Window.

Information about the connection with device 192.168.250.20 is registered in
the Register Device List. Double-click this connection to edit the settings.