Omron SYSMAC CJ1W-EIP21 User Manual

Page 106

Advertising
background image

80

CIO Area Allocations

Section 4-2

Registered Target
Node Table
(EtherNet/IP Unit to
CPU Unit) (n + 16 to n
+ 19)

Words n+16 to n+19 show the registration status of the target nodes that are
connected with the EtherNet/IP Unit as the originator.

These words show the status of nodes 0 to 63 only. If it is necessary to show
the status of nodes higher than node 63, select “user settings” as the layout
pattern. For details, refer to 4-4 User Settings Area.

4

IP Router Table
Error

ON

Unit

ON when the IP router table
information is incorrect.

OFF

Unit

OFF when the IP router table
information is correct.

5

(Not used)

---

---

---

6

Routing Table Error ON

Unit

ON when the routing table
information is incorrect.

OFF

Unit

OFF when the routing table
information is correct.

7 to 8

(Not used)

---

---

---

9

Ethernet Expan-
sion Settings Error

ON

Unit

One of the following parame-
ters is invalid.

• FINS settings

OFF

Unit

OFF when the parameters
above are valid.

10

BOOTP Server
Error

ON

Unit

One of the following errors
occurred when using the
BOOTP server.

• The IP address received

from the BOOTP server is
incorrect.

• A communications timeout

occurred with the server.

OFF

Unit

OFF when the errors listed
above did not occur.

11 to
13

(Not used)

---

---

---

14

Address Mismatch

ON

Unit

ON when the target IP
address conversion method is
set to Automatic generation,
but the local IP address’ host
ID does not match the FINS
node address.

OFF

Unit

OFF when the values match.

15

Non-volatile Mem-
ory Error

ON

Unit

ON when an error occurred in
the Unit’s internal non-volatile
memory.

OFF

Unit

OFF when the Unit’s internal
non-volatile memory is oper-
ating normally.

Bit

Name

Status

Manipulated

by

Unit operation