Maintenance and Replacement

Section 13-1

13-1 Maintenance and Replacement

This section describes the routine cleaning and inspection recommended as
regular maintenance, as well as the Unit replacement procedure required if an
EtherNet/IP Unit needs to be replaced.

13-1-1 Cleaning

Clean the EtherNet/IP Unit regularly as described below in order to keep the
network in its optimal operating condition.

• Wipe the Unit daily with a dry, soft cloth.

• When a spot can’t be removed with a dry cloth, dampen the cloth with a

neutral cleanser (2% solution), wring out the cloth, and wipe the Unit.

• A smudge may remain on the Unit from gum, vinyl, or tape that was left on

for a long time. Remove the smudge when cleaning.

!Caution

Never use volatile solvents such as paint thinner, benzene, or chemical wipes.
These substances could damage the surface of the Unit.

13-1-2 Inspection

Be sure to inspect the system periodically to keep it in its optimal operating
condition. In general, inspect the system once every 6 to 12 months, but
inspect more frequently if the system is used with high temperature or humid-
ity or under dirty/dusty conditions.

Inspection Equipment

Prepare the following equipment before inspecting the system.

Normally Required
Equipment

Have a standard and Phillips-head screwdriver, multimeter, alcohol, and a
clean cloth.

Occasionally Required
Equipment

Depending on the system conditions, a synchroscope, oscilloscope, ther-
mometer, or hygrometer (to measure humidity) might be needed.

Inspection Procedure

Check the items in the following table and correct any items that are below
standard.

13-1-3 Unit Replacement Procedure

Replace a faulty EtherNet/IP Unit as soon as possible. If the built-in EtherNet/
IP port is faulty, replace the CPU Unit as soon as possible. We recommend
having spare Units available to restore network operation as quickly as possi-
ble.

Precautions

Observe the following precautions when replacing a faulty Unit.

• After replacement, verify that there are no errors with the new Unit.

• When a Unit is being returned for repair, attach a sheet of paper detailing

the problem and return the Unit to your OMRON dealer.

Item

Standard

Inspection

Environmental
conditions

Ambient and cabinet temperature

0 to 55

°

C

Thermometer

Ambient and cabinet humidity

10 to 90% (with no condensa-
tion or icing)

Hygrometer

Dust/dirt accumulation

None

Visual

Installation

Are the Units installed securely?

No looseness

Phillips-head
screwdriver

Are the Ethernet cable connectors
fully inserted and locked?

No looseness

Visual