Omron SYSMAC CJ1W-EIP21 User Manual

Page 386

Advertising
background image

360

Connection Status Codes and Error Processing

Section 14-3

01

0109

Error code returned from target:

The connection size settings
are different in the originator
and target.

Check the connection sizes set in the originator and target.

01

0110

Error code returned from target:

The target was unable to open
the connection, because of its
operating status, such as down-
loading settings.

Check whether
the tag data link is
stopped at the tar-
get. (Restart the
tag data link com-
munications with
the control bit.)

Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)

Check whether the
tag data link is
stopped at the origi-
nator. (Restart the
tag data link commu-
nications with the
control bit.)

01

0111

Error code returned from target:

The RPI was set to a value that
exceeds the specifications.

This error does
not occur.

Check the target’s
RPI setting specifica-
tions.

Set the originator’s
RPI setting to 10
seconds or less.

01

0113

Error code generated by origi-
nator or returned from target:

Attempted to open more con-
nections than allowed by the
specifications (CJ2M: 32, other
CPU Units: 256).

Check the con-
nection settings
(number of con-
nections) at the
originator and tar-
get.

Check the connec-
tion settings (number
of connections) at
the originator and
target.

Check the connec-
tion specifications for
another company’s
devices.

Check the connec-
tion settings (number
of connections) at
the originator and
target.

Check the connec-
tion specifications for
another company’s
devices.

01

0114

Error code returned from target:

The Vendor ID and Product
Code did not match when open-
ing connection.

This error does
not occur.

Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)

Confirm that the tar-
get device’s EDS file
is correct.

Check the origina-
tor’s connection set-
tings.

01

0115

Error code returned from target:

The Product Type did not match
when opening connection.

This error does
not occur.

Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)

Confirm that the tar-
get device’s EDS file
is correct.

Check the origina-
tor’s connection set-
tings.

01

0116

Error code returned from target:

The Major/Minor Revisions did
not match when opening con-
nection.

Check the major
and minor revi-
sions set for the
target device and
connection. If nec-
essary, obtain the
EDS file and set it
again.

Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)

Confirm that the tar-
get device’s EDS file
is correct.

Check the origina-
tor’s connection set-
tings.

01

0117

Error code returned from target:

The tag set specified in the con-
nection’s target variables does
not exist.

Check whether
the originator and
target tag sets
and tags are set
correctly.

CJ2 CPU Units
Only: Check sym-
bol settings in the
CPU Unit.

Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)

Check the origina-
tor’s connection set-
tings. Check whether
the target’s tag sets
and tags are set cor-
rectly.
CJ2 CPU Units Only:
Check symbol set-
tings in the CPU
Unit.

Connection status

Source of error

Handling

General

Status

(hex)

Additional

Status

(hex)

Configuration 1

Configuration 2

Configuration 3

Advertising