Using the LED Indicators and Display for Troubleshooting

Section 14-2

---

---

E3

Server Con-
nection Error

An error
occurred in
transmission to
the SNMP trap.

---

03C4

De-
tails:
07xx

Perform one of the
following:

• Correct the

SNMP trap set-
tings.

• Check the com-

munications path
(EtherNet/IP Unit
or built-in Ether-
Net/IP port, cable
connections,
hubs, routers, and
servers) and cor-
rect any prob-
lems.

---

Lit red

F0

IP Address
Duplication

The IP address
of the EtherNet/
IP Unit or built-in
EtherNet/IP port
is the same as
the IP address
set for another
node.

• The Unit will be

offline and unable to
communicate. Errors
will be returned to all
communications
requests.

• Data exchanges

(refreshing) will con-
tinue with the CPU
Unit.

The Unit Error
Occurred Flag (n+10,
bit 00), Network Error
Occurred Flag (n+10,
bit 01), and IP
Address Duplication
Error Flag (n+10, bit
06) will go ON.

0211

Check the IP
addresses set on
other nodes.
Restart the Ether-
Net/IP Unit or built-
in EtherNet/IP port
after correcting the
IP address settings
to eliminate dupli-
cations.

Flashing
red

---

F3

Address mis-
match

The target IP
address conver-
sion method is
set to Automatic
generation
, but
the last byte of
the local IP
address does
not match the
value set on the
Node Address
Setting Switch.

• Operation will con-

tinue with the set IP
address as the local
IP address.
The Address Mis-
match Flag (n+14,
bit 14) will turn ON.

---

Check the IP
address and the
Node Address Set-
ting Switch setting.