Note Best = Recommended; OK = Allowed; --- = Not allowed.

3-4-4

Using Contact Outputs (Common to All Units)

When an EtherNet/IP Unit or built-in EtherNet/IP port and Contact Output Unit
are mounted in the same Rack or connected to the same PLC, communica-
tions errors may occur due to noise generated by the contact outputs. Use
one or more of the following measures when installing Contact Output Units
and EtherNet/IP Units on the same Rack.

Mounting Location

Mount (or connect) any Contact Output Units as far away from the EtherNet/IP
Unit or built-in EtherNet/IP port as possible.

Cable Location

Separate the transceiver cable or twisted-pair cable connecting the EtherNet/
IP Unit as far from the wiring to the Contact Output Units as possible. The
coaxial cable must also be placed as far away from the Contact Output Units
and their wiring as possible.

100 Mbps
(fixed)

Full duplex

---

---

---

Best

---

Half duplex

OK

---

---

---

OK

Switching hub setting

EtherNet/IP Unit setting

Auto-

negotiation

10 Mbps (fixed)

100 Mbps (fixed)

Full

duplex

Half

duplex

Full

duplex

Half

duplex

Contact Output Unit

EtherNet/IP Unit

Contact outputs

To switching hub

Contact Output Unit

EtherNet/IP Unit

Contact outputs

To switching hub