FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports

Appendix E

• An error response will be returned if the IP address conversion method in the system mode settings is set

for automatic generation on the FINS/UDP Tab Page of the Unit.

Response Codes

IP ADDRESS WRITE

Write the local IP address and the subnet mask in the CPU Bus Unit System Setup.

Command Block

Response Block

Parameters

IP Address (Command)

Specify the local IP address of the EtherNet/IP Unit or built-in EtherNet/IP port using 4 pairs of 2-digit hexadec-
imal numbers in the range 00.00.00.00 to FF.FF.FF.FF (0.0.0.0 to 255.255.255.255 decimal). Specify 0.0.0.0 to
enable the local IP address set in the allocated DM Area words.

Example: 150.31.2.83

Subnet Mask (Command)

Specify the local IP address of the EtherNet/IP Unit or built-in EtherNet/IP port using 4 pairs of hexadecimal
numbers in the range 00.00.00.00 to FF.FF.FF.FF (0.0.0.0. to 255.255.255.255 decimal).

Example: 255.255.255.255

Response code

Description

0000

Normal end (echo reply received from the remote node)

1001

Command too large

1002

Command too small

1003

The number of records specified does not match the sent data
length.

110C

The number of records is not between 0 and 32.
The FINS node address is not between 1 and 126
The IP address is 0.

2307

IP address conversion method is set for automatic generation.

27 57

Subnet mask

IP address

Command

code

27 57

Command

code

Response

code

96

53

1F

02

FF

00

FF FF