5 message communications error indications, Message communications error indications – Omron SYSMAC CJ1W-EIP21 User Manual

Page 220

Advertising
background image

194

Message Communications Error Indications

Section 7-5

7-5

Message Communications Error Indications

There are two ways to obtain information on communications errors that occur
in message communications: checking the EtherNet/IP Unit’s error log or
checking its indicators.

1,2,3...

1.

Each time a communications error occurs, an error code is placed in an er-
ror record in the error log stored in RAM in the EtherNet/IP Unit or CPU
Unit with the built-in EtherNet/IP Port. Up to 64 records can be stored in
the error log. The time and date that the error occurred are also recorded
together.

The error log can be read or cleared from the CPU Unit by sending an FINS
command to the EtherNet/IP Unit (Error Log Read/Clear). The contents of
the error log can also be monitored from the Configurator.

2.

When a communications error has occurred, details on the error are indi-
cated by the MS and NS indicators and the 7-segment display on the front
panel of the EtherNet/IP Unit or CPU Unit with the built-in EtherNet/IP port.
This information can be used for troubleshooting.

CPU Unit

Configurator

FINS command

Read-out

Monitor

Code
Code

Code

64 records

Example: Routing table error

Flashing red
Not relevant

NS

MS

Communications status 3

15

00

EtherNet/IP
Unit

CPU
Unit

Advertising