Omron SYSMAC CJ1W-EIP21 User Manual

Page 281

Advertising
background image

255

Receiving Explicit Messages

Section 9-2

Operating mode: Returns the operating mode of the CPU Unit in 1-byte

(2-digit) hexadecimal.
0001 Hex: PROGRAM mode; 0002 Hex: MONITOR mode;
0004 Hex: RUN mode

Fatal error information: Returns the fatal error information for the CPU

Unit in 2 bytes (low to high).

Non-fatal error information: Returns the non-fatal error information for

the CPU Unit in 2 bytes (low to high).

7

6

5

4

3

2

1

0

Bit

Unspecified

Flash memory access status (CS1H, CJ1-H, CJ1M, and CS1D only)

0: Memory is not being written.
1: Memory is being written.

Operation status

0: Stopped (User program is not being executed.)
1: Operating (User program is being executed.)

CPU status

0: Normal
1: CPU standby (waiting for SYSMAC Bus Remote I/O or other event)

Battery status (CS1H, CJ1-H, CJ1M, and CS1D only)

0: No battery
1: Battery installed

-

-

-

-

1: System error (FALS)

1: Cycle time over

1: Program error

1: I/O setting error

1: No. of I/O points exceeded

1: Inner Board fatal error

1: Number duplicate use error

1: I/O Bus error

1: Memory error

Unspecified (reserved for system use)

1: Special I/O Unit error

1: CPU Bus settings error

1: Battery error

1: SYSMAC BUS error

1: Special I/O Unit

1: CS1-series CPU Bus Unit error

1: Inner Board error

1: I/O verification error

1: PLC system error

1: Unspecified (reserved for system use)

1: Basic I/O Unit error

1: Interrupt task error

1: Unspecified (reserved for system use)

1: System error (FAL)