Message Service Transmission Delay

Section 10-5

For details, refer to the CPU Unit’s Operation Manual.

Send Processing

Transmission Delay

The transmission delay time depends on the baud rate set for the EtherNet/IP
Unit or built-in EtherNet/IP port, as shown in the following table. (There may
be additional delays due to the other devices in the network, such as switch-
ing hubs.)

Receive Processing

CPU Bus Unit Service
Cycle (Remote Node)

The following table shows the CPU Bus Unit service cycle, which depends on
the CPU Unit’s CPU processing mode setting.

Note

CJ2 CPU Units support only Normal Mode.

For details, refer to the CPU Unit’s Operation Manual.

CPU Bus Unit Service
Processing Time (Remote
Node)

The following table shows the CPU Bus Unit service processing time, which
depends on the CPU Unit’s CPU processing mode setting.

Command

0.550 ms

Response

(Number of words being transferred

×

0.002) + 0.550 ms

Baud rate

Delay time

100Base-TX Command

0.0118 ms

Response

(Number of words transferred

×

0.0013) + 0.0118 ms

10Base-T

Command

0.0157 ms

Response

(Number of words transferred

×

0.0019) + 0.0157 ms

Command

0.704 ms

Response

(Number of words being transferred

×

0.003) + 0.704 ms

CPU execution mode

Processing time details

Normal Mode (See note.)

One CPU Unit cycle time

Priority peripheral servicing

EtherNet/IP Unit or
built-in EtherNet/IP
port is given prior-
ity.

Time slice instruction execution
time

EtherNet/IP Unit or
built-in EtherNet/IP
port is not given
priority.

One CPU Unit cycle time

Parallel processing with syn-
chronous memory access

One CPU Unit cycle time

Parallel processing with asyn-
chronous memory access

0.2 ms + peripheral servicing time (1 ms max. for
peripheral servicing of each Special I/O Unit, CPU
Bus Unit, peripheral port, RS-232C port, and Inner
Board)

CPU execution mode

Processing time details

Normal Mode (See note.)

4% of CPU Unit cycle time

(10% for CJ2 CPU Units)

Priority peripheral servicing

EtherNet/IP Unit or
built-in EtherNet/IP
port is given prior-
ity.

Time slice peripheral servicing
execution time

EtherNet/IP Unit or
built-in EtherNet/IP
port is not given
priority.

Set peripheral servicing time
(Default: 4% of CPU Unit cycle
time)