6 creating i/o tables, 6-1 i/o table overview, 6-2 connecting programming devices to the plc – Omron SYSMAC CJ1W-EIP21 User Manual

Page 72: 6-3 procedure for creating i/o tables, Creating i/o tables, I/o table overview, Connecting programming devices to the plc, Procedure for creating i/o tables

Advertising
background image

46

Creating I/O Tables

Section 3-6

3-6

Creating I/O Tables

3-6-1

I/O Table Overview

I/O tables are used to identify Units mounted to the PLC, and to allocate I/O to
them. With CS-series and CJ-series PLCs, whenever there is a change to the
Unit configuration it is necessary to create I/O tables and register the mounted
Units in the CPU Unit.

The I/O tables can be created in the following ways.

• Using the CX-Programmer offline.

• Using the CX-Programmer online to create the I/O table based on the

Units mounted to the PLC.

• Using the Programming Console to create the I/O table based on the

Units mounted to the PLC.

• Using the CPU Unit's automatic I/O allocation at startup. (This method is

available for the CJ Series only.)

3-6-2

Connecting Programming Devices to the PLC

To create the I/O tables, connect a Programming Device (such as a CX-Pro-
grammer or Programming Console) to the PLC.

Applicable Programming Devices

The following Programming Devices can be used with CS/CJ-series PLCs.

Programming Console

Note A Programming Console cannot be used with the CJ2H-CPU

@@

(-EIP)

and CJ2M-CPU3

@

CPU Units. Use the CX-Programmer.

CX-Programmer

For information on how to connect and operate the CX-Programmer, refer to
the CX-Programmer Operation Manual (Cat. No. W446).

Connecting a Programming Console

To connect a Programming Console, attach a CS/CJ-series Key Sheet and
then connect the Console to the CPU Unit’s peripheral port. (It cannot be con-
nected to the RS-232C port.)

3-6-3

Procedure for Creating I/O Tables

Programming Console

This section provides the procedure for creating the I/O tables using a Pro-
gramming Console. For details on using the Programming Console, refer to
the Programming Console’s operation manual.

Note

(1) With the CJ Series, it is necessary to create I/O tables only when the user

is allocating I/O manually. With the CS Series, it is always necessary to
create I/O tables.

Model number

Key Sheet (required)

Recommended cable (required)

C200H-PRO27-E

CS1W-KS001-E

CS1W-CN224 (cable length: 2.0 m)
CS1W-CN624 (cable length: 6.0 m)

CQM1-PRO01-E

CS1W-CN114 (cable length: 0.1 m)

Advertising