Omron SYSMAC CJ1W-EIP21 User Manual

Page 42

Advertising
background image

16

EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications

Section 2-1

CJ2 CPU Built-in EtherNet/IP Port

Note

If tag data links are being used, use 100Base-TX. Otherwise, 10Base-T can
be used, but this is not recommended.

Item

Specifications

Model number

CJ2H-CPU

@@

-EIP

CJ2M-CPU3

@

Type

100Base-TX (See note.)

Unit classification

CJ2 CPU Unit built-in port (CJ2 CPU Bus Unit)

CPU Unit
words used

Allocated CIO Area
words (CPU Bus
Unit words)

25 words/Unit (one unit number’s words)

These words contain control bits and flags, the target node PLC’s operating and error
information, Unit status, communications status, registered/normal target node infor-
mation, and FINS/TCP connection status.

Allocated DM Area
words (CPU Bus
Unit words)

100 words/Unit (one unit number’s words)

These words contain the IP address display/setting area.

User-set area

Any usable data area words

Target node PLC’s operating and error information, and registered/normal target
node information

CPU Bus Unit Sys-
tem Setup

Not used.

Non-volatile memory for the CJ2
built-in EtherNet/IP port

The following settings are stored in the non-volatile memory for the built-in EtherNet/
IP port.

Note Unlike the regular Ethernet Units, the CPU Bus Unit Setup Area in the CPU

Unit is not used for these settings.

1. Unit Setup (communications settings for the built-in EtherNet/IP port, such as the

IP address, DNS server settings, host name, baud rate, FINS/UDP settings, and
FINS/TCP settings)

2. Tag data link settings (device parameters)

Transfer
specifica-
tions

Media access
method

CSMA/CD

Modulation method

Baseband

Transmission paths

Star form

Baud rate

100 Mbit/s (100Base-TX)

Transmission media

Shielded twisted-pair (STP) cable

Categories: 100

at 5, 5e

Transmission dis-
tance

100 m (distance between hub and node)

Number of cascade
connections

There is no limitation when a switching hub is used.

Current consumption (Unit)

For CJ2 CPU Units, refer to the CJ2 CPU Hardware Operation Manual (W472).

Weight

Dimensions

Other general specifications

Other specifications conform to the general specifications of the CJ2 or built-in Ether-
Net/IP port CJ2 CPU Unit.

Advertising
This manual is related to the following products: