Backup sources and restore targets, Operating methods – Omron SYSMAC CJ1W-EIP21 User Manual

Page 360

Advertising
background image

334

Simple Backup Function

Section 13-2

Applications

Use the simple backup function when creating a backup data file for the entire
PLC (including the CPU Unit, EtherNet/IP Units, built-in EtherNet/IP port, and
Serial Communications Units/Boards), or when replacing all the Units.

Backup Sources and
Restore Targets

The data that was backed up with the simple backup function can be restored
to Units or built-in ports as shown in the following table. Network Configuration
designations are given for the model numbers and versions of the backup
sources and restore targets.

The model number must be the same for both the backup source and restore
target. The CIP revision must be the same or higher.

Note

(1) Functions added for revision 2.1 will be set to their default settings.

The number of settings will be increased, so an error will occur in the
comparison after data is restored.

(2) Data backed up for revision 1.1 using a simple backup can be restored to

an EtherNet/IP Unit or built-in EtherNet/IP port with revision 2.1, but an
error will occur in the comparison. When changing the unit version, refer
to 6-2-18 Changing Devices for information on the Network Configurator
device change function.

Operating Methods

Backing Up EtherNet/IP
Unit or Built-in EtherNet/IP
Port Setup Files to the
Memory Card

Set pins 7 and 8 of the DIP switch on the front panel of the CPU Unit as
shown in the following table, and press the Memory Card Power Supply
Switch for 3 seconds with the Memory Card inserted into the slot. Release the
switch when the BUSY indicator lights.

CS1

No

---

CJ1-H

---

Yes

CJ1

---

No

CJ1M

---

Yes

CJ2H

---

Yes

CJ2M

---

Yes

CPU Unit

EtherNet/IP Unit

CS1W-EIP21

CJ1W-EIP21

Restore target

CS1W-EIP21

CJ1W-EIP21

CJ2B-EIP21

CJ2M-EIP21

CJ1W-EIP21

(CJ2)

Backup source

Rev. 1.1

Rev. 2.1

Rev. 2.1

Rev. 2.1

Rev. 2.1

CS1W-EIP21, CJ1W-EIP21

Rev. 1.1

Yes

Yes

(See note 1.)

No

No

No

CS1W-EIP21, CJ1W-EIP21

Rev. 2.1

No

Yes

No

No

No

CJ2B-EIP21

Rev. 2.1

No

No

Yes

No

No

CJ2M-EIP21

Rev. 2.1

No

No

No

Yes

No

CJ1W-EIP21 (CJ2)

Rev. 2.1

No

No

No

No

Yes

DIP switch settings

SW7

ON

SW8

OFF

Advertising