Omron SYSMAC CJ1W-EIP21 User Manual

Page 355

Advertising
background image

329

Automatic Clock Adjustment Error Processing

Section 12-4

The error log can be read by sending FINS commands to the EtherNet/IP Unit
or built-in EtherNet/IP port or by using the mail receive function and specifying
the ErrorLogRead command.

Error

code

Meaning

Detailed error code

Correction

EEPROM

1st byte

2nd byte

03C1

Server set-
ting error

00H: DNS
03H:
SNTP
04H: FTP
06H:
BOOTP
07H:
SNMP
08H:
SNMP
Trap
09H:
FINS/
UDP
0AH:
FINS/
TCP

01: IP address

02: Host name

03: Port number

04: Other
parameters

Set the server
settings correctly
based on the
information in the
detailed error
code.

---

03C4

Server
connection
error

00H: DNS
03H:
SNTP
04H: FTP
06H:
BOOTP
07H:
SNMP
08H:
SNMP
Trap

01: Specified
host does not
exist

02: No service
at specified host

03: Timeout

04: Closed uni-
laterally by host

05: Cannot con-
nect because
account infor-
mation does not
match

06: Host name
resolution error

07: Transmis-
sion error

08: Reception
error

09: Other error

0AH: Error in
obtained IP
address

Take either of the
following mea-
sures.

• Correct the set-

tings for each
server.

• Inspect the com-

munications
path (EtherNet/
IP Unit or built-in
EtherNet/IP
port), cable con-
nections, hub,
router, server),
and correct the
situation that is
causing the
error.

---

03C6

Clock data
write error

0001: Clock data could not
be refreshed because of a
CPU Unit error.

Clear the CPU
Unit error.

---

0002: Clock data could not
be refreshed because the
CPU Unit could not write
clock data in that operation
mode.

The automatic
clock adjustment
function is not
supported by cer-
tain CPU Units
(models, lot num-
bers) if they are in
RUN or MONI-
TOR mode.

(See note.)

---