Overview of Tag Data Links

Section 6-1

Note

The I/O memory words used in tags in a tag set do not have continuous
addresses. The tags can also be from different I/O memory areas. To enable a
connection, however, each tag set must include only input tags or only output
tags. (Both input and output tags cannot be included in the same tag set.)

Specifications

The following table shows the tag and tag set specifications.

PLC Status

A characteristic function of the CS1W-EIP21 and CJ1W-EIP21 EtherNet/IP
Units and CJ2 built-in EtherNet/IP ports is the ability to specify the PLC status
as a member of the tag set. This function reads the operating status (operat-
ing and error status) of the CPU Unit of the PLC in which the EtherNet/IP Unit
is mounted, and includes the PLC status as status flags in the data trans-
ferred by the tag data links.

When the PLC status is specified as an output (produce) tag, it is actually
transferred as the tag set’s leading data in the following format.

Tag set SP1_IN
(group of tags a, b, and c)

EtherNet/IP

I/O memory

CPU Unit

a

b

c

d

e

I/O memory

CPU Unit

f

g

h

i

j

Tag set SP1_OUT

Tag set SP2_OUT
(group of tags d, e)

Tag set SP2_IN

Connection

One tag each
(Each tag is set using a text
string of the network symbol
or I/O memory address.)

Tags

Tag sets

CS1W-EIP21
CJ1W-EIP21
CJ2H-CPU

@@

-EIP

CJ2M-CPU3

@

CS1W-EIP21
CJ1W-EIP21
CJ2H-CPU

@@

-EIP

CJ2M-CPU3

@

Total size of all tags

184,832 words

Total size of all tags

640

words

Maximum size of 1 tag set

722 words

(The maximum size is 721
words when the tag set
includes the PLC status.)

Maximum size of 1 tag set

20 words

(The maximum size is 19
words when the tag set
includes the PLC status.)

Maximum size of 1 tag

722

words

(The maximum size is 721
words when the tag set
includes the PLC status.)

Maximum size of 1 tag

20

words

(The maximum size is 19
words when the tag set
includes the PLC status.)

Number of tags per tag set

8

(7 tags/tag set when the tag set includes the PLC status)

Note Input and output variables cannot be combined.

Number of registrable tags

256

Number of registrable tags

32

Number of registrable tag
sets

256

Number of registrable tag
sets

32

15

14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0

0

0

0 0

0 0

0

0

0

0

0

0

0

PLC Operating Flag

PLC Error Flag