Omron SYSMAC CJ1W-EIP21 User Manual

Page 41

Advertising
background image

15

EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications

Section 2-1

CJ-series EtherNet/IP Unit

Note

If tag data links are being used, use 100Base-TX. Otherwise, 10Base-T can
be used, but this is not recommended.

Item

Specifications

Model number

CJ1W-EIP21

Type

100Base-TX (See note.)

Applicable PLCs

CJ-series PLCs

Unit classification

CJ-series CPU Bus Unit

Mounting location

CPU Rack or Expansion Rack

Number of Units that can be
mounted

8 max. (including Expansion Racks)

Note Up to seven EtherNet/IP Units can be connected to a CJ2H-CPU

@@

-EIP CPU

Unit. Up to two EtherNet/IP Units can be connected to a CJ2M CPU Unit.

CPU Unit
words used

Allocated CIO Area
words (CPU Bus
Unit words)

25 words/Unit (one unit number’s words)

These words contain control bits and flags, the target node PLC’s operating and error
information, Unit status, communications status, registered/normal target node infor-
mation, and FINS/TCP connection status.

Allocated DM Area
words (CPU Bus
Unit words)

100 words/Unit (one unit number’s words)

These words contain the IP address display/setting area.

User-set area

Any usable data area words

Target node PLC’s operating and error information, and registered/normal target
node information

CPU Bus Unit Sys-
tem Setup

Not used.

Non-volatile memory within Ether-
Net/IP Unit (See note.)

The following settings are stored in the EtherNet/IP Unit’s non-volatile memory.

Note Unlike the regular Ethernet Units, the CPU Bus Unit Setup Area in the CPU

Unit is not used for these settings.

1. Unit Setup (communications settings for the EtherNet/IP Unit, such as the IP ad-

dress, DNS server settings, host name, baud rate, FINS/UDP settings, and FINS/
TCP settings)

2. Tag data link settings (device parameters)

Transfer
specifica-
tions

Media access
method

CSMA/CD

Modulation method

Baseband

Transmission paths

Star form

Baud rate

100 Mbit/s (100Base-TX)

Transmission media

Shielded twisted-pair (STP) cable

Categories: 100

at 5, 5e

Transmission dis-
tance

100 m (distance between hub and node)

Number of cascade
connections

There is no limitation when a switching hub is used.

Current consumption (Unit)

410 mA max. at 5 V DC

Weight

94 g max.

Dimensions

31

Ч

90

Ч

65 mm (W

×

H

×

D)

Other general specifications

Other specifications conform to the general specifications of the CJ-series.

Advertising