Ip address table write, Response codes, Command block response block parameters – Omron SYSMAC CJ1W-EIP21 User Manual

Page 429: Precautions, Number of records (command), Ip address table records (command)

Advertising
background image

403

FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports

Appendix E

Response Codes

IP ADDRESS TABLE WRITE

Writes the IP address table.

Command Block

Response Block

Parameters

Number of Records (Command)

The number of records to write is specified in hexadecimal between 0000 and 0020 (0 to 32 decimal) in the
command. If this value is set to 0, the IP address table will be cleared so that no records are registered.

IP Address Table Records (Command)

Specify the IP address table records. The number of records specified must be provided. The total number of
bytes in the IP address table records is calculated as the number of records

×

6 bytes/record. The configuration

of the 6 bytes of data in each record is as shown in the following diagram.

FINS Node Address
Node address for communications via the FINS command (hexadecimal).

IP Address
IP address used by TCP/IP protocol (hexadecimal).

Precautions

• The registered IP address table will not be effective until the PLC or EtherNet/IP Unit or built-in EtherNet/IP

port is restarted.

Response code

Description

0000

Normal end

0105

Node address setting error

Local IP address setting error

0302

CPU Unit error; execution not possible.

1001

Command too large

1002

Command too small

1100

Connection number not set from 1 to 16

Number

of records

IP address
table records

Command

code

27 50

IP address
table records

6 bytes

6 bytes

Command

code

Response

code

27 50

FINS node

number

1

00

IP address

6 bytes