4 user settings area, 4-1 overview of the user settings area, 4-2 user settings area – Omron SYSMAC CJ1W-EIP21 User Manual

Page 111: User settings area, Overview of the user settings area

Advertising
background image

85

User Settings Area

Section 4-4

4-4

User Settings Area

4-4-1

Overview of the User Settings Area

When the layout of the allocated CIO Area words is set to user settings, the
user settings area can be used in addition to the allocated CIO Area words
and allocated DM Area words.

The beginning word of the user settings area can be set in the Status Area
Tab Page in the Edit Parameters Dialog Box of the CX-Programmer.

4-4-2

User Settings Area

The user can allocate any available area to contain the registered target node
information, normal target node information, target node PLC operating infor-
mation, and target node PLC error information.

Registered Target
Node Table
(EtherNet/IP Unit to
CPU Unit)

These flags indicate the registration status of the target nodes, and are valid
only when the EtherNet/IP Unit is the originator of the connection. For details
on the default settings, refer to 4-2-2 Details of the Allocated CIO Area Words.

Offset

Bit

Data direction

+0

+15
+16

+31
+32

+47
+48

+63

15

08 07

00

EtherNet/IP Unit

CPU Unit

EtherNet/IP Unit

CPU Unit

EtherNet/IP Unit

CPU Unit

EtherNet/IP Unit

CPU Unit

Registered target node

(16 words)

Normal target node

(16 words)

Target node PLC's operating information

(16 words)

Target node PLC's error information

(16 words)

Bit

Name

Status

Manipulated

by

Unit operation

---

Registered Target
Node Flags

ON

Unit

Indicates that the node’s tag
data link is registered.

OFF

Unit

Indicates that the node’s tag
data link is not registered.

15 14 13 12 11 10 9 8

7

6 5

4

3

2

1

0

+0

15 14 13

12 11 10 9 8 7 6 5 4 3 2 1

0

+1

31 30 29

28 27 26 25 24 23

22 21 20 19

18

17 16

+2

47 46 45

44 43 42 41 40 39

38 37 36 35

34

33 32

+3

63 62 61

60 59 58 57 56 55

54 53 52 51

50

49 48

+4

79 78 77

76 75 74 73 72 71

70 69 68 67

66

65 64

+5

95 94 93

92 91 90 89 88 87

86 85 84 83

82

81 80

+6

111

110

109

108 107

106

105

104

103

102

101

100

99

98

97 96

+7

127

126

125

124 123

122

121

120

119

118

117

116

115

114 113 112

+8

143

142

141

140 139

138

137

136

135

134

133

132

131

130 129 128

+9

159

158

157

156 155

154

153

152

151

150

149

148

147

146 145 144

+10

175

174

173

172 171

170

169

168

167

166

165

164

163

162 161 160

+11

191

190

189

188 187

186

185

184

183

182

181

180

179

178 177 176

+12

207

206

205

204 203

202

201

200

199

198

197

196

195

194 193 192

+13

223

222

221

220 219

218

217

216

215

214

213

212

211

210 209 208

+14

239

238

237

236 235

234

233

232

231

230

229

228

227

226 225 224

+15

255

254

253

252 251

250

249

248

247

246

245

244

243

242 241 240

Advertising