Omron SYSMAC CJ1W-EIP21 User Manual

Page 385

Advertising
background image

359

Connection Status Codes and Error Processing

Section 14-3

Email [email protected]

WEB www.odva.org

The following table shows the possible originator/target configurations.

The following table shows the likely causes of the errors causes for each con-
figuration and connection status (code).

Configuration

Originator

Target

Configuration 1

CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU

@@

-EIP, CJ2M-

CPU3

@

CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU

@@

-EIP, CJ2M-

CPU3

@

Configuration 2

CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU

@@

-EIP, CJ2M-

CPU3

@

Other company’s device

Configuration 3

Other company’s device

CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU

@@

-EIP, CJ2M-

CPU3

@

Connection status

Source of error

Handling

General

Status

(hex)

Additional

Status

(hex)

Configuration 1

Configuration 2

Configuration 3

00

0000

Normal status code:

The connection has been
opened and the tag data link is
communicating normally.

---

---

---

01

0100

Error code returned from target:

Attempted to open multiple con-
nections at the same connec-
tion.

This error does
not occur.

Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer for details on
preventing the error
from occurring in the
future.)

Depends on the orig-
inator’s specifica-
tions.
(Contact the origina-
tor device’s manufac-
turer for details on
preventing the error
from occurring in the
future.)

01

0103

Error code returned from target:

Attempted to open a connection
with an unsupported transport
class.

This error does
not occur.

Confirm that the tar-
get supports Class
1.

Confirm that the
originator supports
Class 1.

01

0106

Duplicate consumers:

Attempted to open multiple con-
nections for single-consumer
data.

If the tag data link
is stopped or
started, this error
may occur accord-
ing to the timing,
but the system will
recover automati-
cally.

Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)

If the tag data link is
stopped or started,
this error may occur
according to the tim-
ing, but the system
will recover automat-
ically.

01

0107

Error code returned from target:

Attempted to close a connec-
tion, but that connection was
already closed.

This error does
not occur.

This error does not
occur.

This is not an error
because the connec-
tion is already
closed.

01

0108

Error code returned from target:

Attempted to open a connection
with an unsupported connection
type.

This error does
not occur.

Check which con-
nection types can be
used by the target.
(Contact the manu-
facturer.)

Only multicast and
point-to-point can be
set.

Check which con-
nection types can be
used by the origina-
tor.

(An error will occur if
a connection other
than multicast or
point-to-point is set.)