Using FINS Applications

Section 8-5

8-5

Using FINS Applications

8-5-1

CX-Programmer (CX-Server)

The following examples show how to connect online from a CX-Programmer
on an Ethernet network to a PLC on the Ethernet network.

System Configuration Example 1: No Routing

In this example, an online connection is made by FINS/UDP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.

Conditions

• FINS/UDP method

• IP Address Conversion: Automatic (Dynamic) generation method

CX-Programmer's Change PLC Dialog Box

CX-Programmer's FINS/UDP Tab Page in Edit Parameters Dialog Box

CX-Programmer/CX-Integrator

Ethernet or EtherNet/IP (Network address: None)

Ethernet port

Target: PLC1

EtherNet/IP Unit

IP address: 192.168.250.1

FINS/UDP method

Node number: 1

IP address conversion: Automatic
generation method (dynamic)

EtherNet/IP Unit node number: 2
EtherNet/IP Unit IP address: 192.168.250.2

Settings for target PLC (PLC1)'s Change PLC Dialog Box

Setting

PLC name

PLC1

Network classification

Ethernet

Network Tab Page

FINS transmission source address

0

FINS destination

Network number

0

Node address

2

Frame length

2,000 bytes

Response monitor time

2 seconds

Driver Tab Page

Workstation node address

1

Automatic generation method

Not selected

IP address

192.168.250.2 (Eth-
erNet/IP Unit or
built-in EtherNet/IP
port IP address)

Port number

9600

Item

Setting

FINS/UDP Port

Default (9600)

IP Address Conversion

Automatic (Dynamic) generation method

IP Router Table

None