1-1 sending explicit messages using cmnd(490), Sending explicit messages using cmnd(490) – Omron SYSMAC CJ1W-EIP21 User Manual

Page 269

Advertising
background image

243

Sending Explicit Messages

Section 9-1

9-1-1

Sending Explicit Messages Using CMND(490)

With a CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP port, a
CMND(490) in the CPU Unit’s ladder program can send CIP UCMM explicit
messages.

Send the CIP UCMM explicit message’s command data in a FINS command
following the 2810 hex FINS command code.

The CIP UCMM explicit message’s response is received following the
2810 hex FINS command code and the FINS completion code.

The following command is used: [ CMND

S

D

C ]

S: First command word

D: First response word

C: First control data word

Command data is set in order starting with the word specified for the
CMND(490) operand S (first command word) and continuing with words with
higher addresses in I/O memory in the command block format.

Command Format Example: Get_Attribute_All Service to Identity Object

Routing service data

Transport

ID

8-bit instance ID: 24 Hex

Priority/Time Tick

Time Out Ticks

Message

request size

8-bit class ID

Class ID identity object

8-bit instance ID: 24 Hex

Instance ID

Ethernet port: 12 Hex

Route path size (13 bytes)

Padding data

Request path

Request path

Routing service data

Routing service data

Last hop data

Route path

size

(8 words)

Service code
Get_Attribute_All service

Request path size (2 words)

Route path

Route path

Request path size = 2 words: 02 Hex

Class ID Connection Manager: 06 Hex

8-bit class ID: 20 Hex

28

10

00

00

05

DC

52

02

20

06

24

01

0A

0C

06

00

01

02

20

01

24

01

08

00

12

0D

31

1

39

9

32

2

.

2E

31

1

36

6

38

8

2E

.

32

2

35

5

30

0

2E

.

32

2

00

Service code

Unconnected Send service: 52 Hex

Command

code

Instance ID

Advertising