Socket status read, Precautions, Response codes – Omron SYSMAC CJ1W-EIP21 User Manual

Page 439: Command block response block parameters, Socket status (response)

Advertising
background image

413

FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports

Appendix E

Precautions

All the above values are set to 0 if Ethernet communications functions are stopped due to improper settings in
the system setup.

These values are cleared when the EtherNet/IP Unit or built-in EtherNet/IP port is started or reset. Values will
be counted only until the maximum values are reached.

Response Codes

SOCKET STATUS READ

Reads the network socket status of the EtherNet/IP Unit or built-in EtherNet/IP port.

Command Block

Response Block

Parameters

Socket Status (Response)

Returns eight types of information in records of 32 bytes each. A maximum of 62 records can be returned. The
format of each record is shown below.

Protocol (4 bytes)
The protocol used for the socket is returned as a number.
00 00 00 06: TCP; 00 00 00 11: UDP

Receive Queue (4 bytes)
The number of bytes in the reception queue.

Send Queue (4 bytes)
The number of bytes in the send queue.

Local IP Address (4 bytes)
The local IP address allocated to the socket.

Local Port Number (4 bytes)
The local port number allocated to the socket.

Remote IP Address (4 bytes)
The remote IP address allocated to the socket.

Response code

Description

0000

Normal end

1001

Command too large

27 64

Command

code

27 64

Socket status

Response

code

Command

code

32 bytes

32 bytes

Socket status