Setting Tag Data Links

Section 6-2

• The Display the detail of Connection Check Box can be used to switch

between device-level and connection-level displays of tag data link com-
munications.

• An asterisk will be displayed after the device name of the originator set for

the connection.

• The Edit Device Parameters Dialog Box can be displayed by selecting a

connection and clicking the Edit Button. The connections can be edited in
this dialog box.

6-2-6

Setting Tags Using Data Link Tool

Using the EtherNet/IP Datalink Tool enables easily setting data links similar to
those for the Controller Link by using only I/O memory addresses. This
method has the following restrictions.

• Settings can be made only for tag data links between OMRON EtherNet/

IP Units and built-in EtherNet/IP ports.

• Tags must be set using I/O memory addresses.

• A maximum of two tags (area 1 and area 2) can be set in one tag set.

Select Network - EtherNet/IP Datalink Tool from the menus in the Network
Configurator after you have registered all the devices to start the EtherNet/IP
Datalink Tool.