Omron SYSMAC CJ1W-EIP21 User Manual

Page 105

Advertising
background image

79

CIO Area Allocations

Section 4-2

Communications
Status 2
(EtherNet/IP Unit to
CPU Unit) (n + 13)

Word n+13 contains status flags related to the Ethernet, as shown in the fol-
lowing diagram.

Communications
Status 3
(EtherNet/IP Unit to
CPU Unit) (n + 14)

Word n+14 contains status flags related to the Ethernet errors, as shown in
the following diagram.

Bit

Name

Status

Manipulated

by

Unit operation

0

FTP Status

ON

Unit

ON when the FTP server is
operating (i.e., when there is
an FTP client connection).

OFF

Unit

OFF when the FTP is on
standby (i.e., waiting for a cli-
ent connection).

1 to 13

(Not used)

---

---

---

14

Link Status

ON

Unit

ON when a link is established
with the switching hub.

OFF

Unit

OFF when the link with the
switching hub is stopped.

15

(Not used)

---

---

---

n+13

15 14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Link Status

FTP Status

Bit

Name

Status

Manipulated

by

Unit operation

0 to 1

(Not used)

---

---

---

2

Basic Ethernet
Settings Error

ON

Unit

One of the following parame-
ters is invalid.

• TCP/IP

Configuration

set-

tings
(IP address, subnet mask, or
Link settings)

OFF

Unit

OFF when the parameters
above are valid.

3

IP Address Table
Error

ON

Unit

ON when the IP address table
information is incorrect.

OFF

Unit

OFF when the IP address
table information is correct.

n+14

IP Address Table Error

IP Router Table Error

Address Mismatch

Basic Ethernet Settings Error

Non-volatile Memory Error

Routing Table Error

Ethernet Expansion Settings Error

BOOTP Server Error

15 14

13

12

11

10

9

8

7

6

5

4

3

2

1

0