Setting Tag Data Links

Section 6-2

1,2,3...

1.

Connect the Network Configurator online.

2.

There are two ways to download the parameters.

• Downloading to All Devices in the Network

Select Network - Download. The following dialog box will be displayed.

• Downloading Individually to Particular Devices

Select the icon of the EtherNet/IP Unit to which you want to download. To
select multiple nodes, press and hold the Shift Key while selecting addi-
tional icons. (In the following example, 2 nodes are selected:
192.168.250.1 and 192.168.250.2.)

After selecting the icons, click the right mouse button over the icon to dis-
play the pop-up menu, and select Parameter - Download.

The following dialog box will be displayed.

3.

Click the Yes Button to download the tag data link parameters to the Eth-
erNet/IP Unit.

The following dialog box will be displayed if any of the CPU Units is not in
PROGRAM mode.

• Display When All EtherNet/IP Units and Built-in EtherNet/IP Ports are

Revision 2 or Higher