Omron SYSMAC CJ1W-EIP21 User Manual

Page 245

Advertising
background image

219

Using FINS Applications

Section 8-5

System Configuration Example 3: Connecting the CX-Programmer Online

Using the FINS/TCP Method

In this example, an online connection is made by FINS/TCP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.

Conditions

• FINS/TCP method

CX-Programmer's Change PLC Dialog Box

CX-Programmer's FINS/TCP Tab Page in Edit Parameters Dialog Box

Not set. (All defaults are used.)

FinsGateway ETN_UNIT Setup

TCP Nodes Tab Page: Ethernet Node Definition Dialog Box

CX-Programmer/CX-Integrator

Ethernet or EtherNet/IP (Network number: none)

Ethernet port

Target: PLC1

EtherNet/IP Unit

Node number: 1
IP address: 192.168.250.1

FinsGateWay Version 2003

IP address conversion: Automatic generation method (dynamic)
EtherNet/IP Unit node number: 2
EtherNet/IP Unit IP address: 192.168.250.2

FINS/TCP method

Settings for target PLC (PLC1)'s Change PLC Dialog Box

Setting

PLC name

PLC1

Network classification

FinsGateway

Network Tab
Page

FINS destination

Network number

0

Node address

2

Frame length

2,000 bytes

Response monitor time

2 seconds

Item

Setting

FINS/TCP Port

Default (9600)

IP Router Table

None

Item

Setting

Node address

2

IP address

192.168.250.2

Destination port number

9600

Keep-alive setting

Selected (yes)