117

Overview of Tag Data Links

Section 6-1

There are both input and output tag sets. Each tag set can contain only input
tags or only output tags. The same input tag cannot be included in more than
one input tag set.

Number of Tags in Tag
Sets

Each tag set can contain one or more tags.

Tag Sets with Only One Tag

With basic Network Configurator procedures, each tag set contains only one
tag.

Tag Sets with Multiple Tags

As shown below, tags can be created in groups. Each tag set can contain up
to 8 tags totaling 20 words for the CJ2M or 722 words for other CPU Units.

Tag ii

Tag i

PLC status

EtherNet/IP

Connection

Tag Set (Input Tags)

Tag set name: SP1_IN

PLC status

Tag a

Tag b

Tag c

Tag g

Originator device

Target device

Tag set name: SP1_OUT

Tag Set (Output Tags)

IP address: #

Connection Information

· Target IP address: #

· Originator tag set: SP1_IN

· Target tag set: SP1_OUT

· Packet interval (RPI)

Tag set SP1_IN
(tag a)

EtherNet/IP

I/O memory

CPU Unit

a

b

I/O memory

CPU Unit

c

d

Tag set SP2_IN
(tag d)

Tag set SP1_OUT
(tag c)

Connection

Tag set SP2_OUT
(tag b)

Connection

One tag each
(Each tag is set using a text
string of the network symbol
or I/O memory address.)