FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports

Appendix E

Precautions

• No response will be returned if the command ends normally. A response will be returned only if an error

occurs.

• In some cases, send requests (SEND(192)/RECV(193) instructions) made from the PLC to the EtherNet/

IP Unit or built-in EtherNet/IP port just before execution of the RESET command may not be executed.

• Applications that use TCP/IP, such as FINS/TCP communications services, are closed immediately before

resetting.

Response Codes

CONTROLLER DATA READ

Reads the following data from the EtherNet/IP Unit or built-in EtherNet/IP port: Model number, version, IP
address, subnet mask, FINS UDP port number, mode settings, Ethernet address.

Command Block

Response Block

Parameters

Model number, Version (Response)

The model number and version of the EtherNet/IP Unit or built-in EtherNet/IP port are returned as ASCII char-
acters occupying 20 bytes each (i.e., 20 characters each). If all bytes are not used, the remaining bytes will be
all spaces (ASCII 20 Hex).

Example Model: CS1W-EIP21, CJ1W-EIP21, CJ2B-EIP21, or CJ2M-EIP21
Example Version: V2.00

By convention, the model number of the built-in EtherNet/IP port on a CJ2H-CPU

@@

-EIP CPU Unit is CJ2B-

EIP21.

By convention, the model number of the built-in EtherNet/IP port on a CJ2M-CPU3

@

CPU Unit is CJ2M-EIP21.

IP Address, Subnet Mask (Response)

The IP address and subnet mask of the EtherNet/IP Unit or built-in EtherNet/IP port are returned as 4 bytes
each.

FINS UDP Port Number (Response)

The UDP port number of the EtherNet/IP Unit or built-in EtherNet/IP port for FINS is returned as 2 bytes.

Response code

Description

1001

Command too large

05 01

Command code

05 01

20 byte

20 byte

4 byte

Subnet

mask

4 byte

FINS UDP

port number

Mode

setting

6 byte

Ethernet address

Response

code

Command

code

Model number

Version

IP address

Advertising