Using the LED Indicators and Display for Troubleshooting

Section 14-2

Errors Related to Memory
Access

The 7-segment display alternates between the node address and error code.

Indicator

Error

Cause

Unit operation (Flag

status)

Error

log

(hex)

Countermeasure

MS

NS

7-segment

Flashing
red

---

E9

Memory
Access Error

An error
occurred in the
Unit's non-vola-
tile memory
itself. This error
will occur in the
following cases.

1. An error oc-

curred while
writing the er-
ror log.

2. An error oc-

curred while
writing the
device pa-
rameters.

Note:
This error does
not indicate
checksum errors
detected when
reading data.

Case 1:
The error record
remains in RAM only.
Subsequent writes to
non-volatile memory
are all ignored. Other
than that, normal
operation continues.
(Error records con-
tinue to be written to
RAM.)

Case 2:
Tag data links and
message communica-
tions will continue
operating.

The Unit Error
Occurred Flag (n+10,
bit 00), Unit Memory
Error Flag (n+10, bit
04), and Non-volatile
Memory Error Flag
(n+14, bit 15) will turn
ON.

0602

Download the Unit
Setup from the tab
pages of the Edit
Parameters Dialog
Box of the CX-Pro-
grammer and
download the
device parameters
from the Network
Configurator. If the
error recurs,
replace the Ether-
Net/IP Unit or (for a
built-in EtherNet/IP
port) the CPU Unit.