58

Tag Data Link Parameters

Section 3-9

The following method can be used to easily set the data links shown in the fol-
lowing figure using a wizard in the EtherNet/IP Datalink Tool.

1,2,3...

1.

Start the Network Configurator, select the applicable EtherNet/IP Unit in
the Tree View on the left, and then paste it into the Device Configuration
Pane on the right.

Note If an EtherNet/IP system has already been installed, you can create a similar

device configuration by connecting to the EtherNet/IP network and selecting
Network

Upload from the menus.

Refer to

6-2-9 Connecting the Network Configurator to the Network

for infor-

mation on connecting.

2.

Select Network

EtherNet/IP Datalink Tool from the menus to start the

EtherNet/IP Datalink Tool.

#1

#2

#3

#1

#2

#3

#3

#1

#2

#3

#1

#2

#2

#1

#3

#2

#1

#3

EtherNet/IP

W0

W0

D50 D50

Node #1: CJ1H-CPU67H

(IP address: 192.168.250.1)

Node #2: CJ1H-CPU67H

(IP address: 192.168.250.2)

Node #3: CJ1H-CPU67H

(IP address: 192.168.250.3)

Area 1

W0

50 words

W50

50 words

W100

50 words

Area 2

D50

100 words

D150

100 words

D250

100 words