1 overview, Overview – Omron SYSMAC CJ1W-EIP21 User Manual

Page 214

Advertising
background image

188

Overview

Section 7-1

7-1

Overview

The message communications functions send command/response messages
between nodes on the Ethernet network. The messages can be sent between
a computer and PLC, between two PLCs, between an OMRON PLC and a
master made by another company, or between slaves. The messages can be
used to send/receive data; read time data, error logs, and other data; or con-
trol operation, e.g., by force-setting/resetting bits.

There are two types of messages: FINS messages and explicit messages.

Item

FINS messages

Explicit messages

Outline

Message communications for
OMRON products that use the
FINS protocol.

Standard ODVA message communi-
cations using the CIP protocol.

Remote
device

• Computer with an Ethernet inter-

face

• OMRON PLCs (with a CS/CJ-

series EtherNet/IP Unit, built-in
EtherNet/IP port, or Ethernet
Unit)

• Computer with an Ethernet inter-

face

• Another company’s masters or

slaves.

• OMRON PLCs (with a CS/CJ-

series EtherNet/IP Unit or built-in
EtherNet/IP port)

Features

• Send and receive the various

FINS commands to provide an
even greater range of services
than the CIP UCMM messages.

• Provide transparency in mes-

sage communications with other
OMRON networks, such as Con-
troller Link, SYSMAC LINK, and
Ethernet.
(CS1/CJ1 CPU Units with unit
version 2.0 or later or CJ2 CPU
Units: Up to 8 levels, CPU Units
with unit version earlier than 2.0:
Up to 3 levels)

• Supports message communica-

tions with other companies’ Ether-
Net/IP devices.

CS/CJ Series

• CS1W-EIP21
• CJ1W-EIP21
• CJ2H-CPU

@@

-EIP

• CJ2M-CPU3

@

Message communications functions

FINS communications function

Explicit message
communications function

Send

Receive

Send

Receive