Troubleshooting with FINS Response Codes

Section 14-6

14-5-5 Message Timeout Problems

14-6 Troubleshooting with FINS Response Codes

The cause of errors that occur when using the SEND(090), RECV(098), or
CMND(490) instructions can be identified from the response codes. (Refer to
the description of Communications Port Completion Codes in 8-6-4 Writing
Programs
for the storage locations of response codes generated by the
SEND(090), RECV(098), or CMND(490) instructions.)

This section describes the completion codes produced by EtherNet/IP Units.
For details on completion codes produced by CPU Units, other CPU Bus
Units, or computers equipped with FINS services, refer to the device’s opera-
tion manual.

The 6

th

, 7

th

, and 15

th

bits of the response codes have specific functions. The

6

th

bit will be ON when a non-fatal error has occurred in the PLC at the remote

node; the 7

th

bit will be ON when a fatal error has occurred in the PLC at the

remote node; and the 15

th

bit will be ON when a network relay error has

occurred. The following table explains the meaning of the completion codes.

Timeout errors
occur frequently in
message services
(CIP UCMM, CIP
Class 3, or FINS).

• When there is a high load in the tag data link, and the CPU

Unit’s cycle time is relatively long or there are messages
coming in from many nodes, the message service response
time may be delayed and messages may be discarded occa-
sionally.

• In this case, the communications load must be reduced by

increasing (slowing) the tag data link’s RPI, reducing the
message load, or increasing the timeout value.

• The tag data link’s bandwidth usage can be checked on the

Monitor Device Window’s Ethernet Information Tab Page.
Refer to 14-1 Checking Status with the Network Configurator
for details.

• The error log error codes that indicate discarded messages

(insufficient memory) due to heavy communications loads
are 0117, 0119, 0123, 0125, 03C2 (detail code

@@

08,

@@

09, or

@@

0A), 03C3, and 03D2. Refer to 14-1 Checking

Status with the Network Configurator for details on reading
the error codes on the Error History Tab Page.

• For information on preventing high loads in FINS communi-

cations, refer to 8-7 Precautions on High Traffic in FINS
Communications
.

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

First byte

Second byte

Bit

PLC Fatal Error Flag

PLC Non-fatal Error Flag

Relay Error Flag

Main response code (RES)

Sub response code (SRES)

Main response

code

Sub response code

Item to check

Likely cause

Corrective action

Value and

meaning

Value and meaning

00

Normal
completion

00

---

---

---

---