128

Setting Tag Data Links

Section 6-2

Creating and Adding Tags

3.

Click the Edit Tags Button. The Edit Tags Dialog Box will be displayed.

Register the input (consume) tags and output (produce) tags separately.

4.

Click the In - Consume Tab, and click the New Button. The Edit Tag Dialog
Box will be displayed.

5.

In the Name Field, enter the character string for the CPU Unit's I/O memory
address or a network symbol (e.g., 100, W100, D0, Input_signal).
Addresses in the following I/O memory areas can be set.

Note (a) The H, W, D, and E characters can also be input in lower case as

h, w, d, and e.

CPU Unit’s data area

Address (Text to input in Name Field.)

CIO Area

0000 to 6143

Holding Area

H000 to H511

Work Area

W000 to W511

DM Area

D00000 to D32767

EM Area

Bank 0 hex

E0_00000 to E0_32767

···

···

Bank 18
hex

E18_00000 to E18_32767