Using FINS Applications

Section 8-5

CX-Programmer's FINS/UDP Tab Page in Edit Parameters Dialog Box

Same as for System Configuration Example 1.

Routing Table Settings and Transfer to Each PLC

Set the routing tables with CX-Integrator, and transfer them.

1.

Using CX-Integrator, connect online, and select Routing table

Settings.

Then create FINS local routing tables (a local network table and a relay
network table).

Example: PLC 1 Routing Table Settings

• Local Network Table

• Relay Network Table

None

Example: PLC 2 and PLC 3 Routing Table Settings

• Local Network Table

• Relay Network Table

In order to relay from PLC2/3 to the final network number 1, it is necessary
to relay via node address 1 (i.e., the Controller Link Unit) on relay network
number 2.

2.

Save the routing table file (File - Save local routing table file).

3.

Next, to connect online, select Communication Settings from the Net-
work Menu. For each PLC, register a PLC with a direct serial connection
(node address: 0), and select it.

4.

With the CX-Integrator, select Work Online from the Network Menu.

5.

Select Tools - Start Routing table, read the saved file, and select Op-
tions - Transfer to PLC
. Click Yes to transfer the routing tables to the con-
nected PLC.

Driver Tab Page

Workstation node address

1

Automatic generation method

Not selected

IP address

192.168.250.2 (Eth-
erNet/IP Unit or
built-in EtherNet/IP
port IP address)

Port number

9600

Unit number

Local network number

0

1

1

2

Unit number

Local network number

0

2

Final network number

Relay network number

Relay node address

1

2

1

Settings for target PLC (PLC3)'s Change PLC Dialog Box