Explicit message send, Response codes, Command block response block response codes – Omron SYSMAC CJ1W-EIP21 User Manual

Page 442: Subnet mask (response)

Advertising
background image

416

FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports

Appendix E

IP Address (Response)

The local IP address set in the CPU Bus Unit System Setup for the EtherNet/IP Unit or built-in EtherNet/IP port
is returned in order starting from the leftmost bytes in hexadecimal. If the local IP address set in the allocated
words in the DM Area is enabled, 0.0.0.0 is returned.

Subnet Mask (Response)

The subnet mask set in the CPU Bus Unit System Setup for the EtherNet/IP Unit or built-in EtherNet/IP port is
returned in order starting from the leftmost bytes in hexadecimal.

Response Codes

EXPLICIT MESSAGE SEND

Sends a explicit request message to the specified object, and receives a response.

The rightmost 8 bits of the remote (destination) IP address are used as the remote MAC ID, and the remote IP
address is the network ID of the local IP address + the rightmost 8 bits of the remote IP address.

Command Block

Response Block

Response Codes

Response code

Description

0000

Normal end

1001

Command too large

28

01

Command

code

Class ID

Instance ID

Service Data

Destination node address

Service Code

468 bytes max.

28

01

Command

code

End

code

Number of

bytes received

Service Data

Destination node address (remote node)

Service Code

498 bytes max.

00

00

Response code

Description

0000

Normal end

0101

The local node’s network has not started up.

0105

Local node setting error (A BOOTP errors occurs, and the IP
address is undetermined.)

0106

Duplicate address error

0201

The remote node’s network has not started up.

0204

Remote node busy, cannot send.

0205

No response returned from remote node. Monitoring timer
timed out.

1001

Command length exceeds maximum command length.

1002

Command length is less than minimum command length.

1004

Command block format does not match.

1005

Header error

Advertising