333

Simple Backup Function

Section 13-2

• If there is a faulty contact, try wiping the contact with a clean, lint-free

cloth dampened with alcohol.

Note

To prevent electric shock when replacing a Unit, always stop communications
in the network and turn OFF the power supplies to all of the nodes before
removing the faulty Unit.

Settings Required
after Unit
Replacement

After a Unit has been replaced, verify that the following steps have been made
correctly.

• Set the node address and unit number.

• Connect the Ethernet cable.

• Set the configuration data (parameter settings) again and download them.

13-2 Simple Backup Function

Overview

The simple backup function can be used to back up not only all of the data in
the CPU Unit, but also all of the data stored in memory in the EtherNet/IP Unit
or data for the built-in EtherNet/IP port. All of this data will automatically be
backed up to the Memory Card.

The simple backup function can be used for the following EtherNet/IP Units
and built-in EtherNet/IP port.

• CS-series EtherNet/IP Unit (CS1W-EIP21) mounted to a CS1D/CS1-

H CPU Unit

• CJ-series EtherNet/IP Unit (CJ1W-EIP21) mounted to a CJ1-H/CJ1M/

CJ2H-CPU

@@

-EIP CPU Unit

• A built-in EtherNet/IP port on a CJ2H-CPU

@@

-EIP/CJ2M-CPU3

@

CPU Unit

When the EtherNet/IP Unit’s setup data is written to the Memory Card using a
simple backup operation, it is stored in the Memory Card as a Unit/Board
backup file with the file name BACKUP

@@

.PRM. (The

@@

digits in the

backup file name indicate the unit address of the EtherNet/IP Unit or built-in
EtherNet/IP port, which is the unit number + 10 hex.)
This backup file is also used when reading data from the Memory Card or
comparing data with a file in the Memory Card.

Note

The following table shows the Units that support the simple backup function.
Confirm that the Units being used support the function.

All setup data

Backup

Restore

Compare

EtherNet/IP Unit

Memory Card
Power Supply Switch

Memory Card

CPU Unit

All data

CPU Unit

EtherNet/IP Unit

CS1W-EIP21

CJ1W-EIP21

CS1D

Yes

---

CS1-H

Yes

---