51

Setting the Local IP Address

Section 3-7

Method 2: Setting the Address in the CPU Bus Unit's Allocated DM Area

With this method, an IP address is not set in the TCP/IP Configuration (left at
its default setting), and an IP address is set in the allocated DM Area words
(the IP Address Display/Setting Area in words m+98 and m+99).

The IP address can be written in the two IP Address Display/Setting Area
words using the CX-Programmer or the Programming Console. To enable the
new IP Address setting, the EtherNet/IP Unit or built-in EtherNet/IP port must
be restarted or the PLC’s power must be turned OFF and then ON again.

Beginning word m = D30000 + (100 x unit number)

The following table shows the various Unit Setup when only the IP Address
Display/Setting Area is set, and the other TCP/IP Configuration settings are
left at their default values.

Method 3: Setting the TCP/IP Configuration from the Network
Configurator

This method can be used to set IP addresses from the CX-Programmer.
For details, refer to

3-8 TCP/IP and Link Settings

.

If the IP address is set in the TCP/IP Tab Page, that IP address setting will be
displayed in the IP Address Display/Setting Area (words m+98 and m+99) in
the DM Area words allocated to the Unit/port.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

m+98

(1)

(2)

(3)

(4)

m+99

(5)

(6)

(7)

(8)

IP Address: (1)(2).(3)(4).(5)(6).(7)(8) (Hex)

Setting

Operating status

IP address

IP address set in words m+98 and m+99 (IP Address Dis-
play/Setting Area) of the DM Area words allocated to the
EtherNet/IP Unit as a CPU Bus Unit

Subnet mask

Determined by class of the IP address

Default gateway

None (IP routing disabled)

Preferred DNS server

None

Alternate DNS server

None

Host name

None

Domain name

None

Baud rate

Auto-detect