Omron SYSMAC CJ1W-EIP21 User Manual

Page 381

Advertising
background image

355

Using the LED Indicators and Display for Troubleshooting

Section 14-2

Errors Related to the
Network

The 7-segment display alternates between the node address and error code.

Indicator

Error

Cause

Unit operation (Flag

status)

Error

log

(hex)

Countermeasure

MS

NS

7-segment

---

---

E1

Ethernet Link
Not Detected

The link with the
switching hub
could not be
detected.

Note This error

will not
occur
when
data links
are not
set for
version
2.0 or
higher.

• The Unit will be

offline and unable to
communicate. Errors
will be returned to all
communications
requests.

• Data exchanges

(refreshing) will con-
tinue with the CPU
Unit.

The Unit Error
Occurred Flag (n+10,
bit 00), Network Error
Occurred Flag (n+10,
bit 01), and Link OFF
Error Flag (n+10, bit
09) will go ON.
The Link Status Flag
(n+13, bit 14) will go
OFF.

03D3

Check the follow-
ing items:

• Is the cable con-

nected?

• Is the cable dam-

aged or loose?

• Is there excessive

noise?