293

Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports

Section 10-4

For example, the maximum and minimum I/O response times would be as fol-
lows for the above system.

Maximum response time:
1.5 ms + 5 ms

×

2 + 12 ms + 10 ms

×

2 + 2.0 ms = 45.5 ms

Minimum response time:
1.5 ms + 5 ms + 10 ms + 2.0 ms = 18.5 ms

Note

If the message service is used at the same time on the CJ2M built-in port, the
tag data link I/O response time will change.