Omron SYSMAC CJ1W-EIP21 User Manual

Page 377

Advertising
background image

351

Using the LED Indicators and Display for Troubleshooting

Section 14-2

Errors Related to the CPU
Unit

The 7-segment display alternates between the node address and error code.

Errors Related to the
Control Bits

The 7-segment display alternates between the node address and error code.

Indicator

Error

Cause

Unit operation (Flag

status)

Error

log

(hex)

Countermeasure

MS

NS

7-segment

Flashing
red

---

HH

CPU Unit
Fatal Error

A fatal error
occurred in the
CPU Unit.

• If the Unit is the orig-

inator of the tag data
link connection, it
stops communica-
tions.

• If the Unit is the tar-

get of the tag data
link connection and
the PLC status is
included in the com-
munications data,
the corresponding
Target Node PLC
Error Flag will be
turned ON.

0015

Eliminate the
cause of the error
in the CPU Unit.

The tag data link
will restart auto-
matically when the
cause of the error
is eliminated.

---

---

---

Output OFF
Error

An Output OFF
(output inhibit)
condition
occurred in the
CPU Unit.

The tag data link’s
send data will be
cleared to 0 in accor-
dance with the Output
OFF settings, and
data transfer will con-
tinue with that data.

---

Turn OFF the CPU
Unit’s Output OFF
Bit (A50015). The
tag data link’s send
data will be
restored automati-
cally when this bit
is turned OFF.

Indicator

Error

Cause

Unit operation (Flag

status)

Error

log

(hex)

Countermeasure

MS

NS

7-segment

---

---

C6

Multiple
Switches ON

Two or more
software
switches were
ON simulta-
neously, or a
second soft-
ware switch was
turned ON
before a prior
operation was
completed.

The error code will be
displayed on the 7-
segment display for
30 seconds, and the
Multiple Switches ON
Error Flag (n+11, bit
14) will go ON.

The error display will
be cleared the next
time that a settings
operation is com-
pleted normally.

---

Execute control bit
operations one at a
time.