Omron SYSMAC CJ1W-EIP21 User Manual

Page 107

Advertising
background image

81

CIO Area Allocations

Section 4-2

Normal Target Node
Table (EtherNet/IP
Unit to CPU Unit)
(n+20 to n+23)

Words n+20 to n+23 show the connection status of the target nodes that are
connected with the EtherNet/IP Unit as the originator. With revision 2 or
higher, the flag turns ON after all data for multiple connections for individual
target devices is refreshed in the CPU Unit. With revision 1, each flag immedi-
ately turns ON when all connections are established.

These words show the status of nodes 0 to 63 only. If it is necessary to show
the status of nodes higher than node 63, select “user settings” as the layout
pattern. For details, refer to 4-4 User Settings Area.

FINS/TCP Connection
Status
(EtherNet/IP Unit to
CPU Unit) (n+24)

Word n+24 shows the status of FINS/TCP connections. For details, refer to
SECTION 8 FINS Communications.

Bit

Name

Status

Manipulated

by

Unit operation

---

Registered Target
Node Flags

ON

Unit

Indicates that the node’s tag
data link is registered.

OFF

Unit

Indicates that the node’s tag
data link is not registered.

n+16

n+17

n+18

n+19

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

15 14 13 12 11

10

9

8

7

6

5

4

3

2

1

0

31 30 29 28 27

26

25

24

23

22

21

20

19

18

17

16

47 46 45 44 43

42

41

40

39

38

37

36

35

34

33

32

63 62 61 60 59

58

57

56

55

54

53

52

51

50

49

48

Bit

Name

Status

Manipulated

by

Unit operation

---

Normal Target Node
Flags

ON

Unit

Revision 1: Flags immediately
turn ON when all connections
are established.

Revision 2 or higher: Flags turn
ON after all data for multiple
connections for the target
device is refreshed in the CPU
Unit.

OFF

Unit

Indicates that the connection is
not established

n+20

n+21

n+22

n+23

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

15 14 13 12 11

10

9

8

7

6

5

4

3

2

1

0

31 30 29 28 27

26

25

24

23

22

21

20

19

18

17

16

47 46 45 44 43

42

41

40

39

38

37

36

35

34

33

32

63 62 61 60 59

58

57

56

55

54

53

52

51

50

49

48

Bit

Name

Status

Manipulated

by

Unit operation

0

FINS/TCP Connec-
tion 1

ON

Unit

Turned ON by the Unit when a
connection is established.

OFF

Unit

Turned OFF by the Unit when
the connection is terminated.

1

FINS/TCP Connec-
tion 2

ON

Unit

Turned ON by the Unit when a
connection is established.

OFF

Unit

Turned OFF by the Unit when
the connection is terminated.

:

:

:

:

:

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

n+24

Advertising