Function library

Positioning control

3.4.13

Program sets (PS)

3−79

l

EDSVS9332P−EXT DE 2.0

3.4.13.3

Point−to−point positioning with changeover of velocity

Purpose

l

Velocity changeover between two positioning processes without stopping.

t

t

t

v

PS 01

PS 02

Accele-

ration 01

v-Traversing 01

Deceleration 01

Target position 01

Final speed 01

v-Traversing 02

Target
position 02

Decele-
ration 02

9300pos056

Fig. 3−30

Point−to−point positioning with velocity changeover

Function

l

PS mode (C1311): Select Absolute PS" or Relative PS".

l

The travel profiles of two subsequent positioning processes are set as in point−to−point
positioning except that one final speed is unequal 0. The final speed is reached when the
target position is reached. Positioning will start at this speed. Positioning will start at this
speed.
Select target position from VTPOS" (selection under C1312/x)
Select traversing speed from VTVEL" (selection under C1313/x)
Select acceleration from VTACC" (selection under C1314/x)
Select deceleration from VTACC" (selection under C1315/x)
Select final speed from VTVEL" (selection under C1316/x)

l

Point−to−point positioning is possible with the positioning modes (C1210) absolute" and

relative positioning".

Tip!

If a PS with final speed unequal 0 is not followed by a positioning, for instance because of a jump
to Program end" or the function Wait for input", the fault message P09 (impermissible
programming) will be activated. The drive brakes to standstill.