Function library, Function blocks – Lenze EVS9332xP User Manual

Page 247

Advertising
background image

Function library

Function blocks

3.5.45

Monitor outputs of monitoring system (MONIT)

3−219

l

EDSVS9332P−EXT DE 2.0

MONIT outputs

MONIT output

Description

CE0

Communication error − automation interface (AIF)

CE1

Communication error − process data input object CAN1_IN

CE2

Communication error − process data input object CAN2_IN

CE3

Communication error − process data input object CAN3_IN

CE4

BUS−OFF state of system bus (CAN)

EEr

External monitoring, triggered via DCTRL

H05

Internal fault (memory)

H07

Internal fault (power section)

H10

Thermal sensor error − heatsink

H11

Thermal sensor error − inside the device

LP1

Motor phase failure

LU

Undervoltage in the DC bus

nErr

Speed control error

NMAX

Maximum speed (C0596) exceeded

OC2

Earth fault − motor cable

OC5

I x t overload

OC6

I

2

x t overload

OC8

I

2

x t overload advance warning

OH

Heatsink temperature > +90

°C

OH3

Motor temperature > +150

°C threshold

(temperature detected via resolver or incremental value encoder)

OH4

Heatsink temperature > C0122

OH7

Motor temperature > C0121
(temperature detected via resolver or incremental value encoder)

OH8

Motor temperature measured via inputs T1 and T2 too high

OU

DC−bus overvoltage

P03

Following error

P16

Faulty transmission of sync telegram on system bus (CAN)

P19

Limitation of input values at X9

PL

Error during rotor position adjustment

Sd2

Resolver error at X7

Sd3

Encoder error at X9

Sd5

Encoder error at X6 pins 1 and 2

Sd6

Thermal sensor error − motor (X7 or X8)

Sd7

Absolute value encoder at X8
Initialisation error or communication error during rotor position adjustment

Sd8

Sin/cos encoder at X8 transmits no or inconsistent data