3.5.44

Motor phase failure detection (MLP)

3−217

l

EDSVS9332P−EXT DE 2.0

3.5.44

Motor phase failure detection (MLP)

Purpose

Motor phase monitoring.

MLP1

Fig. 3−162

Motor phase failure detection (MLP1)

Code

LCD

Possible settings

Important

Lenze

Selection

C0597 MONIT LP1

3

0

Trip

2 Warning
3 Off

Conf. LP1
Configuration of motor phase failure
monitoring

C0599 LIMIT LP 1

5.0

1.0

{0.1}

10.0 Current limit LP1

Current limit for motor phase failure
monitoring

Function

Detailed descriptions of monitoring systems and error messages can be found in the system manual,
document number EDSVS9332P.

The function block MLP1 must be entered in the processing table if the motor phase failure detection
is to be used.