Cancelling stand−by operation

Stand−by operation can be cancelled via two ways:

1. Abortion via FB input POS−STDBY−STP"

2. Abortion via touch−probe signal at terminal X5/E1 ... X5/E4

Abortion via FB input POS−STDBY−STP"

E.g.: Linkage with a digital control signal via a fieldbus or a function block interconnection.

Prg-Start

STDBY-ACT

STDBY-STP

N-IN

PS1

PS2

9300pos036

Stand−by operation is aborted and the drive will be reset to positioning when POS−STDBY−STP =
HIGH. Positioning accelerates /decelerates the drive with the profile parameters of the PS to the
preset final speed of the PS. Further PS functions will only be processed when the final speed has
been reached.

Abortion via touch−probe signal at terminal X5/E1 ... X5/E4

E. g.: For accurate positioning over a mark signal after operation with a digital frequency.

Prg-Start

STDBY-ACT

TP

N-IN

PS1

PS2

0

9300pos037

A TP input has been enabled during stand−by operation. When the TP signal occurs, stand−by
operation is aborted and the drive is reset to positioning. A positioning action follows comprising the
TP residual path and starting from the TP position. The positioning traverses the drive using the profile
parameters of the PS. Only after positioning has been completed, the following PS functions will be
processed.