Second homing speed, Function library – Lenze EVS9332xP User Manual

Page 84

Advertising
background image

Function library

Positioning control

3.4.8

Homing

3−56

l

EDSVS9332P−EXT DE 2.0

Mode 11: Traversing direction to negative POS−LIM−NEG

Travel in negative direction up to POS−LIM−NEG, reverse there and reference to TP. TP can also be
the negative edge of POS−LIM−NEG.

Otherwise identical with mode 10

Tip!

In order to save initiators the limit switch (POS−LIM−xxx) can be simultaneously used as touch probe.
The TP input is selected under C1214.

Since the limit switches are factory−set to LOW active, select the rising edge for TP (C1215/x = 0).
After homing, the drive must not directly stop on the reference point, since this may result in a
response of the travel range limit switches. The reference limit point must be set accordingly.

3.4.8.10

Second homing speed

Second homing speed

A second homing speed (C1241) can be activated by C1216.

Homing procedure with activated second homing speed:

Modes 0, 1:

To POS−REF−MARK at first speed, then at second speed.

Modes 2, 3:

At first speed to limit switch POS−LIM−POS (mode 2) or POS−LIM−NEG (mode 3), second speed after
reversing.

Modes 4, 5:

To limit switch POS−REF−MARK at first speed, second speed after reversing.

Modes 6, 7:

To POS−REF−MARK at first speed, then at second speed.

Modes 8, 9:

Only at first speed to reference point via TP.

Modes 10, 11:

To limit switch POS−LIM−POS or POS−LIM−NEG at first speed, second speed after reversing.