Function library, Function blocks – Lenze EVS9332xP User Manual

Page 310

Advertising
background image

Function library

Function blocks

3.5.69

Variable table − speed (VTVEL)

3−282

l

EDSVS9332P−EXT DE 2.0

Function

A total of 34 table positions is available.

l

Enter fixed setpoints under C1302.

– 30 table positions (VTVEL−No1 ... VTVEL−No30) are available.

– Subcodes (C1302/1 ... C1302/30) define the table position number.

l

Enter variable setpoints under VTVEL−INx.

– Four table positions (VTVEL−No31 ... VTVEL−No34) are available.

– Signal input via function blocks.

– The setpoints must be transmitted to the table positions before the program set starts and

has access to it.

l

C1382 indicates the setpoints (in % of vmax) on the table positions.

– Select table position (C1382/1 ... C1382/34) with subcode.

l

C1383 displays the setpoints (in inc) on the table positions.

– Select table position (C1383/1 ... C1383/34) with subcode.

l

The conversion from v [units/s] to v [inc] is performed according to the formula:

v [inc]

+ v [unitsńs] @

65536 [inc

ńr] @ gear nominator @ 16384

Feed const. [units

ńr] @ gear denominator @ 1000 [1ńs]

Tip!

Entries into the processing table are only required if FB inputs and outputs are used.

Advertising