Function library, Function blocks – Lenze EVS9332xP User Manual

Page 154

Advertising
background image

Function library

Function blocks

3.5.12

BCD decade switch (BCD)

3−126

l

EDSVS9332P−EXT DE 2.0

With handshaking, minimum wiring

Set BCD mode = 1.

BCD_C

B C D x - N E W - D A T A

t

B C D x - D A T A x

B C D x - R E A D

2 n d c y c l e

3 r d c y c l e

1 s t c y c l e

1 s t c y c l e

( 4 i n p u t s )

( I n p u t )

( O u t p u t )

Fig. 3−79

Sequence of handshaking

Function

l

The superimposed control (e.g. PLC) determines the time of data transmission.

l

After the acceptance signal has been sent from the control to BCDx−READ the BCD is read.

– The signal must be sent for every BCD.

– The reading routine of the FB BCD remains in waiting position until the data transmission is

started.

The BCDs are read in the following sequence:

1. Sign

2. BCD 1

3. BCD 2

4. etc.

Transmission sequence of a BCD:

Input/output

Signal

Function

BCDx−DATA1 ...
BCDx−DATA4

Generating data for the first or next BCD via PLC.

BCDx−NEW−DATA

HIGH

Enables the transmission for the next BCD.

BCDx−READ

LOW−HIGH edge

Reading of the BCD data to the FB BCD.

BCDx−NEW−DATA

LOW

Inhibits the transmission for the next BCD.

BCDx−READ

LOW

Set via PLC.