Function library – Lenze EVS9332xP User Manual

Page 111

Advertising
background image

Function library

Positioning control

3.4.13

Program sets (PS)

3−83

l

EDSVS9332P−EXT DE 2.0

Monitoring in stand−by operation

l

Monitoring of the travel range limit switch is active (fault P01, P02).

l

Monitoring of the position limit value is active (fault P04, P05).

l

Continuous operation is possible with relative positioning (1210 = 1). The position values
(POS−SETPOS and POS−ACTPOS) are reset to 0 when reaching half the position limiting
value; the current following error remains the same (no jerk in the drive).

l

The following error monitoring of the positioning (P14, P15) is not active in stand−by operation.

Tip!

Stand−by operation is terminated when the program is reset (see program control) or manual
operation is activated (see manual operation).

l

Firmware version

³ 2.5:

– If the program is interrupted by CINH or QSP stand−by operation is interrupted. After a

renewed program start, stand−by operation will be continued.

– New profile parameters can be accepted in stand−by operation using PARAM−RD.

l

Firmware version < 2.5:

– If the program is interrupted by CINH (controller inhibit) or QSP (see program control)

stand−by operation will be continued. Stand−by operation cannot be aborted. The program
must be restarted.

– The profile parameters and override inputs are not read in again.